While many FLS testing and inspection activities are performed at least once per year, there are several tasks that need to be performed less frequently.  Do not allow these activities to surprise your client with an unbudgeted expense.  Work with your fire protection system maintenance provider to help you budget for these periodic costs.

Component
Specific Inspection
Frequency

 Cylinders – Visual inspection

 5 Year

 Strainers – Visual inspection

 Filters – Visual inspection

 Orifices – Visual inspection

 Interior Check Valves – Visual inspection

 Interior Alarm – Visual inspection

 5 Year

Dry Sprinkler Valves – Visual inspection

Deluge Sprinkler Valves – Visual inspection

Pre-Action Valves – Visual inspection 

Battery Replacement

Dry System Flow Trip Test 

Dry System Air Leakage Test

Discharge Hose Test

Check Valve Test

Replace Initiators

Hydrostatic Testing of Carbon Dioxide, Wet Chemical, and Foam

Hydrostatic Testing of Cartridges associated with Portable Fire Extinguishers and Wheeled Units

Hydrostatic Testing of Carbon Dioxide Hoses Equipped With A Shut-Off Valve

Clean Agent Suppression

 Sprinklers

 Sprinklers

 Sprinklers

 Sprinklers

 Sprinklers

 Sprinklers

 Sprinklers

 Sprinklers

Fire Alarm

 Sprinklers

 Sprinklers

Clean Agent Suppression

Clean Agent Suppression

Clean Agent Suppression

Portable Fire Extinguishers

Portable Fire Extinguishers

 Sprinklers

 Sprinklers

 Sprinklers

 Sprinklers

Standpipe

Standpipe

Standpipe

Standpipe Hoses

Valves / Valve Components

Private Fire Service

Portable Fire Extinguishers

Clean Agent Suppression

Hood Suppression System

Hood Suppression System

Hood Suppression System

Portable Fire Extinguishers

Portable Fire Extinguishers

Sprinklers

Sprinklers

Sprinklers

Gauges – Test or Replace

 Extra-High Temperature / Corrosive Atmosphere

Check Valves – Test or Replace

Internal Obstruction inspection

Full Flow Test – Remote Point

Hose Connection Pressure Reducing Valves (Full Flow)

Hydrostatic Testing – Manual or Dry Standpipes

 Hose Test

Pressure Reducing Valves / Relief Valves (Full Flow)

 Full Flow Test

 Stored-Pressure Extinguisher – Internal Examination

Replace CGA (Compressed Gas Actuator)

Hydrostatic Testing, Cylinder, Cartridge Replacement, and Regulator Test

Wet Chemical Containers

Hose Assemblies

 Hydrotest of Dry Chemical and Clean Agent Extinguishers

Hydrotest of Dry Chemical Hose Equipped with Shut-Off Valve

 Replace Sprinkler Head (Standard Wet System)

 Replace Sprinkler Head (Dry System)

 Replace Sprinkler Head (Quick Response System)

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

3-5 Years, per Manufacturer Recommendation

 3 Year

 3 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Year

 5 Years For New Hoses, Every 3 Years Thereafter

 5 Year

 5 Year

 6 Year

 10 Year

 12 Year

 12 Year

 12 Year

 12 Year

 12 Year

After 50 Years and Every 10 Years Thereafter

Every 10 Years

After 20 Years and Every 10 Years Thereafter